KYN61-40.5(Z) Metal-Clad, Center-Panel Switchgear
+
  • KYN61-40.5(Z) Metal-Clad, Center-Panel Switchgear

Product Overview
KYN61-40.5(Z) refers to an armored, withdrawable, AC metal-enclosed switchgear (hereinafter referred to as the switchgear), which is a complete indoor power distribution device for three-phase AC systems with a frequency of 50 Hz and a rated voltage of 40.5 kV. It is used in power plants, substations, and industrial and mining enterprises for the reception and distribution of electrical energy, providing functions such as circuit control, protection, and monitoring, and is also suitable for applications involving frequent switching operations.
Scope of Application
The KYN61-40.5(Z) metal-clad, center-mounted switchgear is designed in accordance with the armored, metal-enclosed switchgear specified in GB 3906. It is suitable for three-phase AC power systems with a rated voltage of 40.5 kV and a rated frequency of 50 Hz, and is used for receiving and distributing electrical energy as well as for controlling, protecting, and monitoring circuits. In addition to widespread application in general power systems, it can also be employed in locations subject to frequent switching operations.
Applicable Environment
1. Maximum ambient air temperature: +40°C; minimum: -10°C; daily average temperature not exceeding 35°C.

2. Altitude does not exceed 1000 m
3. The daily average relative ambient humidity shall not exceed 95%, and the monthly average shall not exceed 90%.
4. Seismic intensity shall not exceed Grade 8.
5. The daily average water vapor pressure shall not exceed 2.2 kPa, and the monthly average shall not exceed 1.8 kPa.
6. Locations free from fire hazards, explosion risks, severe pollution, chemical corrosion, and violent vibrations
Relevant Standards
IEC 60694 and GB 11022: General Technical Conditions for High-Voltage Switchgear

IEC 60298 and GB 3906: “Alternating-Current Metal-Enclosed Switchgear”

IEC 60056 and GB 1984: “High-Voltage AC Circuit Breakers”
IEC 60470 and GB/T 14808: “AC High-Voltage Contactors and Contactor-Based Motor Starters”

Technical Indicators
Rated voltage: 40.5 kV
Power-frequency withstand voltage: 95 kV, 1 min
Impulse withstand voltage: 185 (kV)
Rated frequency: 50 Hz
Rated current: 1250/1600/2000 (A)
Rated thermal withstand current: 25/31.5/40 kA for 4 s; Rated dynamic withstand current: 63/80 kA.
Rated short-circuit breaking current: 25/31.5/40 (kA, 4 s)
Rated short-circuit making current: 63/80 (kA)
Rated voltages for the switching and auxiliary circuits: DC 24, 36, 48, 60, 110, 220 V; AC 110, 220 V.
Protection rating: IP3X


KYN61-40.5(Z) Metal-Clad, Center-Panel Switchgear
+
  • KYN61-40.5(Z) Metal-Clad, Center-Panel Switchgear

KYN61-40.5(Z) Metal-Clad, Center-Panel Switchgear


Order(MOQ) :

1 pieces

Payment :

T/T、L/C、D/P、Western Union、Paypal

Product Origin :

Nantong China

Color :

Customized

Lead Time :

30 days


Share to:



Get A Quote

We will contact you within one working day. Please pay attention to your email.

Request Quote

We will contact you within one working day. Please pay attention to your email.

SUBMIT